electrical power panel

electrisity control box
Air-insulated switchgear
Scope of application:
Applicable to three-phase AC rated voltage 12kV, rated frequency 50Hz power system.
factory general control box
Product Details
I. Overview
28A-12(Z)(S1-12) armored removable AC metal-enclosed switchgear is suitable for three-phase AC rated voltage 12kV, rated frequency 50Hz power system. It is mainly used in power plants, substations, power distribution centers of industrial and mining enterprises and large high-voltage motor starting equipment, etc., for receiving and distributing electric energy, and controlling, protecting and monitoring circuits; it can be used for single bus, single bus segmented system or double bus system.
This product complies with the requirements of GB3906 “3~35kV AC Metal-enclosed Switchgear”, GB/T11022 “Common Technical Requirements for High-voltage Switchgear and Control Equipment Standards”, IEC60298 “AC Metal-enclosed Switchgear and Control Equipment with Rated Voltages Above 1KV and 52KV and Below”, and DL/T404 “Technical Conditions for Ordering Indoor AC High-voltage Switchgear”.
- Normal use conditions,
- Ambient temperature: maximum temperature +40℃, minimum temperature -15℃;
- Ambient humidity: daily average not more than 95%, monthly average not more than 90%;
- Altitude: below 1000 meters;
- Earthquake resistance: earthquake intensity not exceeding 8 degrees;
- Daily average water vapor pressure not exceeding 2.2Kpa, monthly average not exceeding 1.8kpa;
- The surrounding air should not contain obvious pollution such as corrosive or flammable gases and water vapor;
- No serious dirt and frequent severe vibration;
- When used under normal environmental conditions exceeding those specified in GB3906, the user and the manufacturer shall negotiate.
Note: ① When the relative humidity is greater than 70%, the electric heater should be connected.
② Where the altitude exceeds 1000m, it shall be handled in accordance with the provisions of JB/Z102-71.
- Model and meaning

distribution electrical panel
IV. Structural features
- The cabinet structure is made of aluminum-zinc plate assembled through multiple bending; high precision, corrosion resistance, light weight, high strength, and strong versatility of spare parts.
- It can be equipped with VS1 (ZN63) series or imported VD4 series vacuum circuit breakers, with wide applicability and high reliability.
- The trolley is equipped with working and test positions, and each position has positioning and display devices, which is safe and reliable.
- It can be equipped with voltage transformer trolleys, metering trolleys, isolation trolleys, station transformer floor trolleys and other trolleys with the same purpose, which are interchangeable;
- It is simple to replace the circuit breaker and has good interchangeability;
- Safe, reliable and effective “five-protection” locking to prevent misoperation;
- The cabinet is equipped with an observation window to observe the working status of the components in the cabinet;
- The protection level is high to prevent the invasion of debris and pests; the protection level of the switch cabinet shell reaches IP4X, and the protection level of each compartment is IP2X;
- The cabinet can be installed against the wall, maintained in front of the cabinet, and the floor space is reduced;
- Each high-voltage room has a pressure relief channel to ensure personal safety;
- The cable room has ample space and can connect multiple cables;
- Heaters can be installed in the circuit breaker room and cable room respectively to prevent condensation and corrosion.
- Lighting devices can be installed in the circuit breaker room and cable room according to user requirements to facilitate maintenance and repair.
V. Technical parameters
rlrunter | name | unit | data | |||
1 | Rated vcltage(maximum operating woltage) | KV | 3.6 7.212 | |||
2 | Rated frequency | Hz | 50 | |||
3 | Gircuit breaker rated curren | A | 63012501600200025003150 | |||
4 | Switchgear rated current | A | 63012501600200025003150 | |||
5 | Ratedthermal stability current(4s) | KA | 16202531.54050 | |||
6 | Rated dynamic stabllity current (peak walue | KA | 40506380100125 | |||
7 | Red ahort-dcutbrmikngeuert | KA | 16202531.54050 | |||
8 | Rated short-circuit making current (peak walue) | KA | 40506380100125 | |||
9 | Rd rauonsalerp ed | hnpowrfrsqueney wthatantheste | KV | 24 | 32 | 42 |
ujtginpkhstandwotag | KV | 40 | 60 | 75 | ||
10 | Protection leve | The houslngls P4X,and the compartment and ciroult breskar room doors are openIP2X |
automation electrical panel
VI. Ordering Instructions
- Main circuit scheme or main circuit system diagram;
- Control circuit electrical schematic diagram, terminal arrangement diagram;
- Switchgear layout plan;
- Cabinet color (if no requirements, according to company standards);
- List of components in the cabinet (including component name, specification model and quantity);
- List of required spare parts;